Control Cable

PARAMETERS

 

Voltage :

These cables can be used on AC voltage up to & Including 1100 V or DC up to & including 1500 V.

 

Size :

1.5 Sq.mm. & 2.5 Sq.mm. upto 61 Cores

 

Conductor:

Annealed Bare Electrolytic Copper/ Aluminum Conductor conforming to IS:8130:1984.

  Insulation: Conductors are insulated with PVC Compound as per IS:5831:1984.
 

Colour of Cores:

Cores are identified with a colour scheme as per IS:1554 (pt-1):1988 as under

2 Cores   - Red & Black
3 Cores - Red, Yellow & Blue
3½ & 4 Cores - Red, Yellow, Blue & Black.
  (Reduced Neutral Core in case of 3½ Core).
5 Cores - Red, Yellow, Blue, Black and Grey

In case of cable exceeding five cores, two adjacent (counting and direction cores) in each layer shall be colored Blue, Yellow and remaining cores grey, or identification by numbers printed over insulation as per IS:1554 (pt-1):1988

  Laying of Cores: Cores are laid up with a suitable lay. The final layer direction shall be kept right hand lay.
  Inner Sheath: The Inner Sheath is applied over laid up of cores by extrusion / wrapping of thermoplastic material.
  Armouring:

It is applied over inner sheath. It may consist of galvanized Round Steel wires or galvanized Flat Steel Strips conforming to IS 3975.  Round Wire armouring is provided, where the calculated diameter under armour is 13.0 mm. Above this, armouring is either round wire/steel strip.

  Outer Sheath

A final covering of PVC Compound, conforming to IS:5831:1984, is applied over Armouring in case of Armoured Cable or over Inner Sheath in case of Unarmoured cable,  called as “Outer Sheath”.  The Insulation, Inner Sheath or Outer Sheath can be HR PVC, FRLS PVC or FRHF  Compound , depending upon their application.

CROSS SECTIONAL DIAGRAM

 
As per IS:1554 (Part-1):1988
 